Opening process:
The operating mechanism drives the spindle to rotate.
The insulation rod drives the contact to separate, forming an air gap (such as a 110kV level gap of ≥ 1 meter).
Arc extinguishing chamber (if any) extinguishes the arc (only for special designs with load disconnection).
Closing process:
The insertion depth of the contact is ≥ 90% of the rated stroke.
Contact pressure ≥ 150N (typical value), reduce contact resistance.
Mechanical locking prevents misoperation.
key technology
Contact design:
Use finger shaped or rolling contacts to reduce contact resistance (such as ≤ 40 μ Ω).
Silver coating thickness ≥ 20 μ m, resistant to arc erosion.
Insulation technology:
Composite insulators (such as silicone rubber jackets) have better pollution flashover resistance than ceramic insulators.
Creepage distance ≥ 31mm/kV (Class IV polluted area).
Operating mechanism:
The energy storage time of the spring mechanism is ≤ 15s, and the opening and closing time is ≤ 0.1s.
The hydraulic mechanism has a pressure range of 16~20MPa and is equipped with an abnormal pressure alarm.
Application scenarios
Substation:
Cooperate with circuit breakers to achieve busbar segmentation and switching operations.
Typical configuration: GW4-126 type is used for 110kV busbar isolation.
Transmission line:
Isolate the faulty section during line maintenance, such as the GW7-252 type used for 220kV lines.
power plant:
Isolation on both sides of the generator outlet circuit breaker, such as GN30-40.5 type used for 40.5kV generator outlet.